To be able to give you benefit and enlarge our business, we also have inspectors in QC Team and assure you our greatest service and products for
System Zoning Thermostat
,
Electrically Actuated Flow Control Valve
,
Air Handler Flow Meter
, We also ensure that your selection will be crafted with the highest quality and reliability. Please feel free to contact us for further information.
PriceList for Controlli Actuator -
ExS6061NS-10/20/30 Explosion-proof Actuator – Soloon Detail:
Model Description of ExS6061NS-10/20/30 Explosion-proof Actuator

| Model
Para. |
ExS6061NS-10DF/24V |
ExS6061NS-10DF/230V |
ExS6061NS-20DF/24V |
ExS6061NS-20DF/230V |
ExS6061NS-30DF/24V |
ExS6061NS-30DF/230V |
| Torque |
10Nm |
20Nm |
30Nm |
| Damper Size |
1m2 |
3m2 |
4.5m2 |
| Power Supply |
AC220V AC24V DC24V 50/60Hz i ≤0.2A
AC220V 50/60Hz |
| Consumption |
7W run/3W remain |
10W run/3W remain |
12W run/3W remain |
| Wire Size |
10VA |
| Connection cable |
Power:1m cable 4*0.5 m2 |
| Auxiliary Switch (F): 1m cable 6*0.5 m2 |
| Running Time |
Motor≤150s |
| Angle of Rotation |
Max 93º |
| Position Indication |
Mechanical indicator |
| Weight |
5Kg |
| Life Cycle |
≥10000 cycles |
| Sound Level |
50dB(A) |
| Protection Level |
Ⅲ(safety low voltage) |
Ⅱ(full insulation) |
| IP Protection |
IP66 |
| Ambient Temperature |
-20~+60℃ |
| Ambient Humidity |
5~95%RH |
| Explosion-proof Mark |
Ex db ⅡB T6 Gb
Ex tb IIIC T85°C Db |
ExS6061NS-10/20/30DF/24(230)V
Features of ExS6061NS-10/20/30 Explosion-proof Actuator
- Single control
- Form-fit 12x12cm shaft
- Universal shift plug
- Two auxiliary switches
- Cast aluminum housing, compacting type
- Safety meets IP66
Meet the Following Standard of ExS6061NS-10/20/30 Explosion-proof Actuator
IEC60079-0:2017, EN60079-0:2012+A11:2013
Electrical Apparatus for Explosive Gas Atmospheres,General Requirements
IEC60079-1:2014, EN60079-1:2007
Electrical Apparatus for Explosive Gas Atmospheres,Explosion-proof
Type: flame-proof
IEC60079-31:2013,EN60079-31:201
Equipment dust ignition protection by enclosure “t”
Usage and Maintenance of ExS6061NS-10/20/30 Explosion-proof Actuator
- The matching thread size of the cable joint and shell is M16 × 1.5, and the diameter of the cable is Φ 6 – Φ 8. The cable joint shall have an Explosion-proof certificate.
- The tightening torque of the ground terminal is 2N. m, Tightening torque of Flameproof joint is 3.2N.m., External ground bolt M4X6, compressing 4mm² conductors.
- It is strictly prohibited to disassemble or open the cover without permission, and do not open the cover with electricity; please do not open it in dangerous occasions; wipe it with wet cloth when opening it.
- The interface shall be equipped with an explosion-proof certified cable gland and have compatible protection mode.
- In addition to the use of the installation manual, during assemble, operation and maintenance, the operator shall comply with the requirements of EN 60079-14
- The maintenance and repair shall meet the requirements of EN 60079-19.
Electrical connection and out line:

What is HVAC Air Duct Damper Actuator?
The Function of HVAC Air Duct Damper Actuator
Product detail pictures:
Related Product Guide:
Our personnel are generally within the spirit of continuous improvement and excellence, and using the excellent top quality goods, favorable rate and superior after-sales expert services, we try to win every customer's believe in for
PriceList for Controlli Actuator -
ExS6061NS-10/20/30 Explosion-proof Actuator – Soloon , The product will supply to all over the world, such as: Hongkong
, Seattle
, Canada
, Ensuring high product quality by choosing the best suppliers, we have also implemented comprehensive quality control processes throughout our sourcing procedures. Meanwhile, our access to a large range of factories, coupled with our excellent management, also ensures that we can quickly fill your requirements at the best prices, regardless the order size.