Manufactur standard Valve Actuator Controller -
S6061SF-10/15 Fire Smoke Damper Actuator – Soloon Detail:
Features of S6061SF-10-15 Fire Smoke Damper Actuator
- ON/OFF or 0-10V
- Shaft size up to 12* 12mm
- Two fixed auxiliary switches
- With IP54 standard
- Without Manuel Override
- 72℃ thermal sensor are optional
Technical Datasheet of S6061SF-10-15 Fire Smoke Damper Actuator
| Item |
S6061SF-10DF(S)/24V |
S6061SF-10DF(S)/230V |
S6061SF-10AF/24V |
S6061SF-15DF(S)/24V |
S6061SF-15DF(S)/230V |
S6061SF-15AF/24V |
| Torque |
10Nm |
15Nm |
| Damper area |
2m2 |
3m2 |
| Power supply |
24VAC/DC; 230VAC 50/60Hz, |
| Operating Power Consumption |
5W |
6W |
| At end stops Power Consumption |
2.5W |
2.5W |
| Wire size |
10VA |
7VA |
10VA |
7VA |
| Connection cable |
D type power:1m cable 2*0.75 m2 A type power:1m cable 4*0.5 m2 |
| Auxiliary switch (F):1m cable 6*0.5 m2 |
| Thermal sensor(S):1m cable 2*0.5 m2 |
| Control signal |
On/off |
0~10V |
On/off |
0~10V |
| Running time |
motor≤100S;spring return≤20S |
motor≤130S;spring return≤20S |
| Rotation angle |
0~90°(Max 93º) |
| Indicate |
Mechanical indicator |
| Weight |
2.6Kg |
| Life cycle |
70000 |
| Noise level |
50dB(A) and 62dB(A) |
| Electric level |
Ⅲ |
Ⅱ |
Ⅲ |
Ⅲ |
Ⅱ |
Ⅲ |
| IP protection |
IP54 |
| Ambient Temperature |
-20~+50℃ |
| Ambient Humidity |
5~95%RH |
| Standard |
CE & UL |
Diagram and Dimension of S6061SF-10-15 Fire Smoke Damper Actuator

Auxiliary Switch of S6061SF-10-15 Fire Smoke Damper Actuator

Dimension of S6061SF-10-15 Fire Smoke Damper Actuator

72℃ thermal sensor
Including: environment(TS1) and damper thermal sensor (TS2);
when the temperature over 72℃, TS1 will be cut;
when the pipe temperature over 72℃, TS2 will be cut.

What is HVAC Air Duct Damper Actuator?
The Function of HVAC Air Duct Damper Actuator
Product detail pictures:
Related Product Guide:
We're committed to furnishing easy,time-saving and money-saving one-stop purchasing support of consumer for
Manufactur standard Valve Actuator Controller -
S6061SF-10/15 Fire Smoke Damper Actuator – Soloon , The product will supply to all over the world, such as: Puerto Rico
, Brazil
, Sheffield
, Our continual availability of high grade products in combination with our excellent pre-sale and after-sales service ensures strong competitiveness in an increasingly globalized market. welcome new and old customers from all walks of life to contact us for future business relationships and mutual success!