Sticking towards the theory of Super Good quality, Satisfactory service ,We are striving to become a superb business enterprise partner of you for Motorized Flow Control Valve , Programmable Ac Thermostat , Motorized Ball Valve 2 Inch , You would not have any communication problem with us. We sincerely welcome customers all over the world to contact us for business cooperation.
OEM Factory for Hvac Sensor Types - S6011-RT/RTH Series of Temperature Transmitter & Temperature-Humidity Transmitter – Soloon Detail:

Operation voltage DC 24V
Output signal 0~10V or 4-20mA
Measuring range Temperature 0~50℃
Humidity 0~100%RH
Measuring Accuracy Temperature ±1℃ or ±0.5℃
RH ±5%RH or ±3%
Ambient temperature -20℃~60℃
Storage -40℃~70℃, non-condensing
Housing ABS

Dimensions of S6011-RT/RTH Series of Temperature Transmitter & Temperature-humidity Transmitter

s6011-rt-rth-series-of-temperature-transmitter-temperature-humidity-transmitter-2

S6011-RT Wiring diagram of S6011-RT/RTH Series of Temperature Transmitter & Temperature-humidity Transmitter

s6011-rt-rth-series-of-temperature-transmitter-temperature-humidity-transmitter-3

S6011-RTH Wiring diagram of S6011-RT/RTH Series of Temperature Transmitter & Temperature-humidity Transmitter

s6011-rt-rth-series-of-temperature-transmitter-temperature-humidity-transmitter-4

Mounting of S6011-RT/RTH Series of Temperature Transmitter & Temperature-humidity Transmitter

  • The transmitters are suitable for direct wall mounting or ceiling mounting using four screw holes on the base. The wiring must be inserted from the back. For mounting:
  • Choose an appropriate location to achieve good control of the ambient temperature. The room transmitters only sense the temperature or humidity at the location where it is mounted.
  • The transmitters should not be mounted close to windows or doors in order to avoid draught. On the other hand, sufficient air circulation must be ensured in order to sense the actual temperature of the room.
  • Place insulation material in the wiring conduit in order to prevent the introduction of air from outside the room.
  • The transmitter should not be exposed to direct radiation or to the sun as this could lead to inaccurate measurement.

Product detail pictures:

OEM Factory for Hvac Sensor Types -
 S6011-RT/RTH Series of Temperature Transmitter & Temperature-Humidity Transmitter   – Soloon detail pictures


Related Product Guide:

Dedicated to strict top quality command and considerate purchaser support, our experienced staff customers are always available to discuss your necessities and be certain full client gratification for OEM Factory for Hvac Sensor Types - S6011-RT/RTH Series of Temperature Transmitter & Temperature-Humidity Transmitter – Soloon , The product will supply to all over the world, such as: UAE , Colombia , Danish , Look forward to the future, we'll focus more on the brand building and promotion . And in the process of our brand global strategic layout we welcome more and more partners join us, work together with us based on mutual benefit. Let's develop market by fully utilizing our in depth advantages and strive for building.
Contact Us Product Inquiry
Contact Us
If you are interested in our products.
Please fill in the form & Contact Us.
+86 10 67863711