Model Description of ExS6061NS-10/20/30 Explosion-proof Actuator

| Model
Para. |
ExS6061NS-10DF/24V |
ExS6061NS-10DF/230V |
ExS6061NS-20DF/24V |
ExS6061NS-20DF/230V |
ExS6061NS-30DF/24V |
ExS6061NS-30DF/230V |
| Torque |
10Nm |
20Nm |
30Nm |
| Damper Size |
1m2 |
3m2 |
4.5m2 |
| Power Supply |
AC220V AC24V DC24V 50/60Hz i ≤0.2A
AC220V 50/60Hz |
| Consumption |
7W run/3W remain |
10W run/3W remain |
12W run/3W remain |
| Wire Size |
10VA |
| Connection cable |
Power:1m cable 4*0.5 m2 |
| Auxiliary Switch (F): 1m cable 6*0.5 m2 |
| Running Time |
Motor≤150s |
| Angle of Rotation |
Max 93º |
| Position Indication |
Mechanical indicator |
| Weight |
5Kg |
| Life Cycle |
≥10000 cycles |
| Sound Level |
50dB(A) |
| Protection Level |
Ⅲ(safety low voltage) |
Ⅱ(full insulation) |
| IP Protection |
IP66 |
| Ambient Temperature |
-20~+60℃ |
| Ambient Humidity |
5~95%RH |
| Explosion-proof Mark |
Ex db ⅡB T6 Gb
Ex tb IIIC T85°C Db |
ExS6061NS-10/20/30DF/24(230)V
Features of ExS6061NS-10/20/30 Explosion-proof Actuator
- Single control
- Form-fit 12x12cm shaft
- Universal shift plug
- Two auxiliary switches
- Cast aluminum housing, compacting type
- Safety meets IP66
Meet the Following Standard of ExS6061NS-10/20/30 Explosion-proof Actuator
IEC60079-0:2017, EN60079-0:2012+A11:2013
Electrical Apparatus for Explosive Gas Atmospheres,General Requirements
IEC60079-1:2014, EN60079-1:2007
Electrical Apparatus for Explosive Gas Atmospheres,Explosion-proof
Type: flame-proof
IEC60079-31:2013,EN60079-31:201
Equipment dust ignition protection by enclosure “t”
Usage and Maintenance of ExS6061NS-10/20/30 Explosion-proof Actuator
- The matching thread size of the cable joint and shell is M16 × 1.5, and the diameter of the cable is Φ 6 – Φ 8. The cable joint shall have an Explosion-proof certificate.
- The tightening torque of the ground terminal is 2N. m, Tightening torque of Flameproof joint is 3.2N.m., External ground bolt M4X6, compressing 4mm² conductors.
- It is strictly prohibited to disassemble or open the cover without permission, and do not open the cover with electricity; please do not open it in dangerous occasions; wipe it with wet cloth when opening it.
- The interface shall be equipped with an explosion-proof certified cable gland and have compatible protection mode.
- In addition to the use of the installation manual, during assemble, operation and maintenance, the operator shall comply with the requirements of EN 60079-14
- The maintenance and repair shall meet the requirements of EN 60079-19.
Electrical connection and out line:

What is HVAC Air Duct Damper Actuator?
The Function of HVAC Air Duct Damper Actuator
Product detail pictures:
Related Product Guide:
The incredibly rich projects administration experiences and a person to 1 service model make the substantial importance of organization communication and our easy understanding of your expectations for
Best Price on Globe Valve With Pneumatic Actuator -
ExS6061NS-10/20/30 Explosion-proof Actuator – Soloon , The product will supply to all over the world, such as: Saudi Arabia
, Lithuania
, Paraguay
, With the goal of zero defect. To care for the environment, and social returns, care employee social responsibility as own duty. We welcome friends from all over the world to visit and guide us so that we can achieve the win-win goal together.