Soloon Controls (Beijing) Co., Ltd. +86-10-67886688
English English English
Soloon Controls (Beijing) Co., Ltd.
Soloon Controls (Beijing) Co., Ltd.
Contact Us
S6067 PN16 Internal thread BSP DN15-DN50

S6067 PN16 Internal thread BSP DN15-DN50

S6067.. PN16 Internal thread BSP DN15-DN50

Application of S6067 PN16 Internal thread BSP DN15-DN50


Used for pre-set control of pipeline flow, this series of products are mainly used to solve the problem of hydraulic imbalance in the fluid transmission and distribution network. According to the system design, it is determined that the branch water supply is constant under the premise of different openings and pressure differences.

The KMF.. balancing valve delivers accurate hydronic performance in an impressive range of applications. Ideally suited for use on the secondary side in heating and cooling systems, and tap water systems.


Features of S6067 PN16 Internal thread BSP DN15-DN50


  • The static balance valve has a precise design, simple structure, and accurate parameters. After the product is installed, the flow should be debugged to meet the flow under the premise of setting the pressure difference. It is an energy-saving product.

  • Used in heating or cooling water systems.

  • Shutdown function.

  • The maximum stroke locking function, when the system is commissioned, can be turned on to provide convenience for future pipeline maintenance and repair. After maintenance or repair, the valve can be directly restored to the set maximum stroke to avoid secondary debugging.

  • The valve carries a measurement joint, which is convenient for quick connection with the measurement equipment and saves debugging time.

  • Can be installed in the water supply or return water pipeline.


Material of S6067 PN16 Internal thread BSP DN15-DN50


DN

DN15-DN50

DN50-DN300

Body

Brass

Nodular cast iron

Seals

EPDM

EPDM

Spool

Brass

Brass


Permissible Media of S6067 PN16 Internal thread BSP DN15-DN50


Medium

Low-temperature hot water,

medium temperature hot water,

chilled water, water with antifreeze

Recommendation: Water treatment

Medium temperature

-10~110℃

PN class

PN16


Types and Technical Data of S6067 PN16 Internal thread BSP DN15-DN50


Product number

DN

Connections

PN

L

H

S6067.. PN16 Internal thread BSP DN15-DN50

6067.15

15

1/in

Internal thread (BSP)

PN16

80

114

6067.20

20

3/in

85

116

6067.25

25

1 in

98

119

6067.32

32

11/in

110

136

6067.40

40

11/in

120

138

6067.50

50

2 in

150

148


6068.65

65

Flanged

(ISO7005-2/ GB 17241.6)


290

285

S6067.. PN16 Internal thread BSP DN15-DN50

6068.80

80

310

324

6068.100

100

350

355

6068.125

125

400

410

6068.150

150

480

477

6068.200

200

600

613

6068.250

250

730

740

6068.300

300

850

828

6068.350

350

980

970

6068.400

400

1100

1100


Kv values of S6067 PN16 Internal thread BSP DN15-DN50


Internal thread (DN15-50)


Product number

DN

No of turns

0.25

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

6067.15

DN15

0.21

0.35

0.48

0.55

0.74

0.97

1.36

1.72

2.06

2.36

2.72

6067.20

DN20

0.34

0.51

0.71

0.92

1.15

1.35

1.62

2.05

2.60

3.13

3.67

6067.25

DN25

0.55

0.94

1.54

2.07

2.57

3.10

3.70

4.43

5.5

5.94

6.73

6067.32

DN32

0.59

1.04

2.05

2.91

4.03

5.10

6.02

6.86

7.65

8.63

9.70

6067.40

DN40

1.22

2.65

4.14

5.75

7.35

8.72

10.03

11.22

12.35

13.83

15.25

6067.50

DN50

-

2.70

5.05

7.15

9.15

11.66

14.22

16.35

18.52

20.72

22.95


Product number

DN

No of turns

5.5

6

6.5

7

7.5

8

8.5

9

9.5

10


6067.15

DN15

3.05

3.42

3.70

3.90

-

-

-

-

-

-

-

6067.20

DN20

4.25

4.90

5.45

5.70

-

-

-

-

-

-

-

6067.25

DN25

7.33

7.90

8.42

8.90

-

-

-

-

-

-

-

6067.32

DN32

10.72

11.72

12.80

13.90

15.04

16.14

17.15

18.16

18.90

19.42

-

6067.40

DN40

17.36

19.44

20.96

22.43

23.62

24.80

25.42

26.07

26.82

27.50

-

6067.50

DN50

24.52

26.07

27.74

29.40

31.12

32.75

34.72

36.70

37.96

38.80

-


Flanged (DN65-400)



No of turns

Product number

6068.65

6068.80

6068.100

6068.125

6068.150

6068.200

6068.250

6068.300

6068.350

6068.400

DN 65

DN 80

DN 100

DN 125

DN 150

DN 200

DN 250

DN 300

DN 350

DN 400

0.5

1.8

2

2.6

5.4

6.6

-

-

-

-

-

1

3.4

4

6

10.4

12

-

-

-

-

-

1.5

4.8

6

9

15.4

22

-

-

-

-

-

2

6.6

8

11.5

21.5

40

40

90

-

-

-

2.5

9.3

11

16

27

65

50

110

-

-

-

3

16.3

14

26

36

100

65

140

150

109

125

3.5

25.5

19.6

44

55

135

90

195

230

129

148

4

35.4

29

63

83

169

120

255

300

148

171

4.5

44.5

41

80

114

207

165

320

370

170

208

5

52

55

98

141

242

225

385

450

207

264

5.5

60.6

68

115

167

279

285

445

535

254

326

6

66

80

132

197

312

340

500

620

302

386

6.5

73

92

145

220

340

400

545

690

352

449

7

77

103

159

249

367

435

590

750

404

515

7.5

80.6

113

175

276

391

470

660

815

471

590

8

85

120

190

300

420

515

725

890

556

680

9

-

-

-

-

-

595

820

970

784

890

10

-

-

-

-

-

650

940

1040

957

1140

11

-

-

-

-

-

710

1050

1120

1100

1250

12

-

-

-

-

-

765

1185

1200

1260

1400

13

-

-

-

-

-

-

-

1320

1420

1560

14

-

-

-

-

-

-

-

1370

1610

1730

15

-

-

-

-

-

-

-

1400

1760

1940

16

-

-

-

-

-

-

-

1450

1870

2140

17

-

-

-

-

-

-

-

-

1960

2280

18

-

-

-

-

-

-

-

-

2040

2410

19

-

-

-

-

-

-

-

-

2130

2530

20

-

-

-

-

-

-

-

-

2200

2630

21

-

-

-

-

-

-

-

-

-

2710

22

-

-

-

-

-

-

-

-

-

2780



Measuring Accuracy of S6067 PN16 Internal thread BSP DN15-DN50


The zero position is calibrated and must not be changed.


Deviation of flow at different settings


The curve (Fig. 1) is valid for valves with normal pipe fittings (Fig.2). Try also to avoid mounting taps and pumps, immediately before the valve.


S6067.. PN16 Internal thread BSP DN15-DN50


Fig.2


S6067.. PN16 Internal thread BSP DN15-DN50


Adjust the scale of the handwheel according to the design requirements.

Exhaust devices should be installed in the system piping, and the system can contain air, which may cause media blockage, failure of the adjustment function, or excessive noise;

It is recommended to add a filter or clean the pipeline at the water inlet of the valve to avoid large particles of impurities blocking the valve control element;

Pay attention to the protection of the detection hole, if it is touched or deformed, it will cause leakage or difficult maintenance in the future.


Setting off of S6067 PN16 Internal thread BSP DN15-DN50


S6067.. PN16 Internal thread BSP DN15-DN50


Adjust the scale of the handwheel according to the design requirements.

This valve has the function of presetting the maximum flow rate. Use a hexagonal wrench to rotate the maximum opening limit core clockwise, so that the maximum opening of the valve can be limited, and subsequent system maintenance will not require debugging.


Application Method of S6067 PN16 Internal thread BSP DN15-DN50


The balance valve can be used alone to control the flow of the system, or it can be used in conjunction with the differential pressure valve. When the valve is installed, the water flow direction must be consistent with the direction of the arrow on the valve. In order to ensure the measurement accuracy, please ensure that there are straight pipe sections before and after the valve(Fig.2)


S6067.. PN16 Internal thread BSP DN15-DN50


The Manufacturer of HVAC Control Valves and Valve Actuators The Manufacturer of HVAC Control Valves and Valve Actuators
The HVAC Actuator Valve Working Principle The HVAC Actuator Valve Working Principle
HVAC Control Valves and Actuators HVAC Control Valves and Actuators
Contact Us Product Inquiry
Contact Us
If you are interested in our products.
Please fill in the form & Contact Us.
+86-10-67886688